Hledání
Search result:
Film Rotary Evaporator Volume 0.88 m3 Rotor Revolutions 550 rpm Weight 470 kg Evaporator height 5,055 mm Stator diameter Φ 700 mm Max. output 240 dm3/h.
Area 11.2 ha Number of storage boxes in a row / total 20 / 80 Box sizes 18 × 6 × 5.5 m Usable box volume 510 m3 Storage box capacity 90 containers FCC volume 3.1 m3 Total storage capacity 10,800 containers Total useful storage volume 33,480 m3
Primary circuit Reactor type KS 150 Reactor's thermal output 560 MWt Fuel natural uranium Amount of fuel 24,600 kg Moderator D2O Amount of moderator 57,200 ...
Specific activity of the waste 106 -108 Bq.dm-3 Main RA-nuclides and compounds Cs, Co, Sr, NaBO2, KNO3 Evaporator heating temperature 180–185 °C Evaporator type film rotor 2S Bitumen AP – 80 soft type Salts to bitumen ratio 30–50 mass % Product density 1.15–1.25 g.cm-3
Number of cooling towers per unit 2 - height 120 m - bottom diameter 84.4 m - upper diameter 53 m
Number of MCPs per unit 6 Input of electric motor 2 MW Voltage 6 kV Revolutions 1,500 rev/min Coolant flow 6,500–7,100 m3/h
Fuel pellet - diameter 7.6 mm - height 15 mm Shell material alloy of zircon and niobium Fuel rod Number of fuel rods in assembly 126 - diameter 9.1 mm - height 2,500 mm Number of operation assemblies 276 Number of regulation assemblies 37 Number of shield assemblies 36 Fuel charge 42 t
Type of reactor WWER 440 / V230 Reactor's thermal output 1,375 MWt Coolant and Moderator demineralized water Reactor's pressure vessel Sizes - diameter 3,840 mm - ...
Number of steam generators per unit 6 Inner sizes - length 11,800 mm - diameter 3,210 mm Weight 145 t Steam output 452 t/h Steam pressure 4.6 MPa Steam temperature 256 °C Temperature of feeding water 158–223 °C Number of heat exchange pipes 5,536 Heat exchange surface 2,510 m2
Number of TGs per unit 2 Nominal output 220 MW Revolutions 3,000 rev/min Steam temperature (HP part) 256 °C Steam pressure (HP part) 4.