| Number of reactor units |
2 |
| Reactor electric output |
440 MW |
| Reactor type |
WWER 440 / V 230 |
| Reactor thermal output |
1,375 MWt |
| Coolant and Moderator |
demineralized water |
| |
|
| Reactor |
|
| Reactor pressure vessel |
|
| Sizes - diameter |
3,840 mm |
| - height |
11,800 mm |
| - weight |
215 t |
| Material |
carbon low-alloy steel |
| |
|
| Reactor active zone |
|
| - diameter |
2,880 mm |
| - height |
2,500 mm |
| Number of fuel assemblies |
276 |
| - shape |
hexagonal |
| - diameter |
144 mm |
| - height |
3,200 mm |
| Number of shielding assemblies |
36 |
| Number of fuel rods in one assembly |
126 |
| - diameter |
9.1 mm |
| - height |
2,500 mm |
| Shell material |
zircon and niobium alloy |
| Number of regulator assemblies |
37 |
| - shape |
hexagonal |
| - diameter |
144 mm |
| Fuel capacity |
42 t |
| Input cooling water temperature |
265 ± 2 °C |
| Output water temperature |
294 ± 2 °C |
| Water pressure |
12.26 MPa |
| |
|
| Steam generator |
|
| Number of steam generators per unit |
6 |
| Sizes |
|
| - length |
11,800 mm |
| - diameter |
3,210 mm |
| - weight |
145 t |
| Steam output |
452 t/h |
| Steam pressure |
4.6 MPa |
| Steam temperature |
256 °C |
| Feeding water temperature |
158–223 °C |
| Number of heat exchange pipes |
5,536 |
| Heat exchange surface |
2,510 m2 |
| |
|
| Main circulation pump |
|
| Number of MCPs per unit |
6 |
| Electric motor input |
2 MW |
| Voltage |
6 kV |
| Revolutions |
1,500 rpm |
| Coolant flow |
6,500–7,100 m3/h |
| |
|
| Turbo generator |
|
| Number of TGs per unit |
2 |
| Nominal output |
220 MW |
| Revolutions |
3,000 rpm |
| Steam temperature (HP part) |
256 °C |
| Steam pressure (HP part) |
4.3 MPa |
| Steam temperature (LP part) |
216.5 °C |
| Steam pressure (LP part) |
0.363 MPa |
| Output voltage |
15.75 kV |
| Cooling |
water / hydrogen |
| |
|
| Condenser |
|
| Number of condenser bodies |
2 |
| Design |
two-part, double chamber |
| Amount of cooling water |
35,000 m3/h |
| Max. cooling water temperature |
33 °C |
| Number of heat exchange pipes |
29,480 |
| Heat exchange surface |
16,300 m2 |
| Condensers cooling method |
circulation |
| |
|
| Cooling towers |
|
| Number of cooling towers |
4 |
| Type of tower |
natural draft |
| - height |
120 m |
| - bottom diameter |
84.4 m |
| - upper diameter |
53 m |